OrderID: Customer Number: Order Status: Device Type: Manufacturer: Model Number: Serial Number: Service: Engineer: Date In: ETA: Completion Date: Problem Description: VFD randomly trips on F0002 Repair Actions: BOP has been disassembled and cleaned. VFD's parameters database was saved on file. Measured incoming voltage was over the VFD's higher limit which is 480VAC. Customer was advised to install a step down transformer. Comments: F0002 Overvoltage Cause - DC link voltage (r0026) higher than the overvoltage threshold (refer to parameter r0026) - ground fault Diagnosis & Remedy Please check the following: - is the line supply voltage within the permissible range? - has the DC current DC link monitoring been enabled (P1240) and correctly parameterized? - extend the deceleration ramp (ramp-down time P1121, P1135) - remove the ground fault - is the required braking power within the permissible limits?
OrderID:
Device Type: Manufacturer: Model Number: Serial Number:
Service:
Engineer: Date In: ETA: Completion Date:
Problem Description: VFD randomly trips on F0002
Repair Actions:
BOP has been disassembled and cleaned. VFD's parameters database was saved on file. Measured incoming voltage was over the VFD's higher limit which is 480VAC. Customer was advised to install a step down transformer. Comments:
F0002 Overvoltage Cause - DC link voltage (r0026) higher than the overvoltage threshold (refer to parameter r0026) - ground fault Diagnosis & Remedy Please check the following: - is the line supply voltage within the permissible range? - has the DC current DC link monitoring been enabled (P1240) and correctly parameterized? - extend the deceleration ramp (ramp-down time P1121, P1135) - remove the ground fault - is the required braking power within the permissible limits?
© Copyright ServoTech Electronics A3-26 Elm Street, Kitchener, Ontario, N2G 2G4 Tel: 519-342-6641 ■ Fax: 1-866-866-9424